The reasons for gate valve stuffing box leakage are as follows:
1. The packing is not compatible with the corrosiveness, temperature and pressure of the working medium;
2. The filling method is wrong, especially if the whole packing is placed in a circle, it is most likely to cause leakage;
3. The valve stem has insufficient machining accuracy or surface finish, or has ovality, or has notches;
4. The valve stem has pitted or rusted due to lack of protection in the open air;
5. The valve stem is bent;
6. The filler has been used for too long and has aged;
7. Excessive operating force.
The method to eliminate packing leakage is:
1. Correct selection of packing;
2. Fill the packing in the correct way;
3. The valve stem must be repaired or replaced if the processing is unqualified, and the surface finish must be at least ▽5, and more importantly, it must be above ▽8, and there are no other defects;
4. Take protective measures to prevent rust, and replace the rusted ones;
5. The bend of the valve stem should be straightened or updated;
6. The packing should be replaced after a certain period of use;
7. Pay attention to stable operation, open and close slowly, to prevent sudden temperature changes or medium impact.